Raychem 5VPL4-CT - VPL4 at 480V and 400V - Power Limiting Trace Heating Cable

More from VPL Power-Limiting Heating Cables

Raychem 5VPL4-CT - VPL4 at 480V and 400V - Power Limiting Trace Heating Cable
Raychem 5VPL4-CT - VPL4 at 480V and 400V - Power Limiting Trace Heating Cable
Raychem 5VPL4-CT - VPL4 at 480V and 400V - Power Limiting Trace Heating Cable
nVent
  • 10-Year Warranty
  • High temperature fluopolymer conductor insulation
  • Hazardous, Zone 1, Zone 2 (Gas), Zone 21, Zone 22 (Dust) Ordinary
  • Temperature maintenance up to 235°C (depending on cable type)

View full description

Quick Find: 10055
Part Code: P000000678

Free Delivery Available
£48.80
£58.56 inc VAT
List Price: £54.50

Selected Total: £0.00


    Qty

    nVent RAYCHEM VPL is a family of power limiting heating cables designed for pipe and equipment heat-tracing in industrial applications.

    VPL can be used for frost protection and process temperature maintenance requiring high power output and/or high temperature exposure. VPL can provide process temperature maintenance up to 235°C (depending on cable type) and can withstand routine steam purges and temperature exposure to 260°C with power off.

    Power-limiting cables are parallel heaters formed by a coiled resistor alloy heating element wrapped around
    two parallel conductors. The distance between conductor contact points forms the heating zone length. This parallel construction allows it to be cut-to-length and terminated on-site. The power output of VPL heating cables decreases with increasing temperature. VPL heating cables can be overlapped once. The relatively flat power temperature curve of VPL ensures a low start-up current and high output at elevated temperatures. VPL cables are approved for use in hazardous areas. Approvals are listed below.

    Application

    Area Classification:

    • Hazardous, Zone 1, Zone 2 (Gas), Zone 21, Zone 22 (Dust)
    • Ordinary

    Traced Surface Type:

    • Carbon steel
    • Stainless steel
    • Painted or unpainted metal

    Chemical resistance:

    • Organics and corrosives
    • For aggressive organics and corrosives consult your local Pentair representative

    Approvals

    The VPL heating cables are approved for use in hazardous areas by Baseefa Ltd.

    • Baseefa06ATEX0188X & IECExBAS06.0048X
    • II 2GD & Exe II T* (see schedule) Ex tD A21 IP66
    • Ex e II T* (see schedule) Ex tD A21 IP66​

    *By design. Temperature classification (T-rating) has to be established by using the principles of stabilized design or the use of a temperature limiting device. Use TraceCalc design software or contact Pentair.

    Maximum Circuit Length

    Based on type 'C' circuit breakers according to EN 60898

    Electrical Protection SizingStart Up TemperatureMaximum Heating Cable length per circuit(M)
    16 A-20°c1951007050
    +10°c2151107555
    25 A-20°c22015510580
    +10°c222015511585
    32 A-20°c220155130100
    +10°c220155130110
    40 A-20°c220155130110
    +10°c220155130110

    *The maximum heating cable length must not exceed these values, even when voltage adjustment factors are used.
    The above numbers are for circuit length estimation only. For more detailed information please use the Pentair TraceCalc software or contact your local Pentair representative.

    Pentair requires the use of a 30 mA residual current device to provide maximum safety and protection from fire.
    Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven.

     Cable208 V230 V254 V277 V400 V480 V
    Maximum maintain or continuous exposure temperature (power off)5VPL2-CT235°c230°c225°c225°c--
    10VPL2-CT220°c210°c200°c195°c--
    15VPL2-CT200°c180°c145°c105°c--
    20VPL2-CT150°c150°c----
    5VPL4-CT----230°c230°c
    10VPL4-CT----215°c205°c
    15VPL4-CT----195°c160°c
    20VPL4-CT----150°c150°c

    Technical specifications

    BrandnVent
    Maximum intermittent exposure temperature (power off)260 °C
    Minimum bend radiusAt -60°C: 20 mm
    Minimum installation temperature-60 °C
    Model5VPL4-CT
    Temperature ClassificationTo be established using the principles of stabilized design or the use of a temperature limiting device.
    VoltageVPL2 at 480 and 400 V

    Videos

    Product downloads

    10-Year Warranty

    File Size: 514.61 KB

    Data Sheet

    File Size: 392.40 KB

    Data Sheet

    File Size: 10.10 MB

    Declarations of Conformity

    File Size: 145.25 KB

    DNV Approval Certificate

    File Size: 367.38 KB

    More from the Raychem VPL Power Limiting Heating Cable range