Raychem 20FHT2-CT Constant Wattage Parallel Heating Cable, 230 V, 20 W/m

Raychem 20FHT2-CT Constant Wattage Parallel Heating Cable, 230 V, 20 W/m
Raychem 20FHT2-CT Constant Wattage Parallel Heating Cable, 230 V, 20 W/m

View full description

Quick Find: 10063
Part Code: 1244-006061

Price on Application

Please contact our sales team for pricing.

Call us on

01473 276672

E-mail us at

sales@traceheatinguk.co.uk

Contact us online

Request pricing

Product overview

Range Raychem FHT2 Constant Wattage Cable
Model 20FHT2-CT

FMT and FHT are constant wattage parallel circuit heating cables designed for pipe and equipment heat-tracing in industrial applications. This family offers an economical alternative to self-regulating heating cables but requires more skill for installation and also requires more advanced control and monitoring systems.

Technical specifications

Cold lead length1.5 m
ColourGreen
Maximum intermittent exposure temperature (power off)260 °C
Minimum bend radius25 mm
Minimum Clearance50 mm
Minimum installation temperature-60 °C
Supply Voltage190 - 277 VAC

Product downloads

Frequently asked questions

Can I use heat trace on plastic pipes?

Yes, when using trace heating on plastic pipes ensure that ATE- 180 aluminium tape is used to help disperse the heat around the pipe.

Read more

Can you design a full surface heating system for me?

Yes, utilising our in-house design facilities, we can design your complete trace heating requirement.

Read more

Do I have to allow extra heat for pumps and valves?

If the surface area of the pump is substantially greater than that of the adjoining pipework then extra heating cable may need to be considered (depending on wattage of cable installed). Pumps and ...

Read more

Do I have to spiral the trace heating onto the pipe?

Most applications can simply be straight traced, reducing costs of materials and installation time without compromising on operational requirements.

Read more

Do I need to use thermal insulation?

Yes, thermal insulation is required on all heat trace applications. Without insulation, surface heat losses can increase approximately 4-5 times.

Read more

Does my trace heating system require maintenance?

Generally, no maintenance of our trace heating systems is required but it is recommended that the system is checked for operational and electrical integrity periodically or prior to the winter or p...

Read more

How do I terminate the heating cable?

Full termination instructions are provided with all our heating tapes

Read more

How do I test my trace heating system is working properly?

System checks depend on the system installed, constant wattage systems can be fully checked for insulation resistance and continuity. Self regulating systems can only be checked for insulation resi...

Read more

What is heat tape for water pipes?

When water pipes are exposed to cold temperatures either outdoors, underground or in small spaces, you can protect them from freezing by wrapping them with heat tape. Heating tape is actually a cor...

Read more

What is Heat Trace?

This is used for a pipe freeze protection application. Electric heat tracing, heat tape or surface heating, is a system used to maintain or raise the temperature of pipes and vessels. Trace heat...

Read more

What is self regulating heating tape?

Self limiting / self regulating heating tape adjusts heat output to equal the heat loss from the pipe work. As pipe temperature falls the electrical conductivity of the semi-conductive core increas...

Read more