Raychem XPI-S-810 Heating Cable Reinforced (7J) 810 ?/km ATEX

Raychem XPI-S-810 Heating Cable Reinforced (7J) 810 ?/km ATEX
Raychem XPI-S-810 Heating Cable Reinforced (7J) 810 ?/km ATEX

Quick Find: 9454
Part Code: 1244-003071

Price on Application

Please contact our sales team for pricing.

Call us on

01473 276672

E-mail us at

sales@traceheatinguk.co.uk

Contact us online

Request pricing

Product overview

XPI-S is a polymer insulated (PI) series heating cable, suitable for use in hazardous areas. It has been designed for use in freeze protection and temperature maintenance applications of pipes, tanks and other equipment. XPI-S is a re-enforced version of XPI, particularly suitable for areas with high demands on mechanical abuse of the heating cable. XPI-S offers an economical solution for a wide variety of heat-tracing applications, in particular for pipe lengths beyond the maximum circuit lengths of parallel heating cables (e.g. 250 m).

The inner insulation is a sandwich construction of high temperature fluoropolymer and PTFE, the outer insulation is made of PTFE. This unique construction is very easy to terminate, highly flexible and makes XPI a very safe and reliable product. It provides highest chemical withstand and most excellent mechanical strength, in particular at elevated temperatures.

XPI-S heating cables can be used for temperatures up to 260°C (continuous) and 300°C (intermittent short-term exposure). XPI-S is easy to install and has printed meter-marks. Pentair offers XPI-S heating cables in a very wide range of resistances, starting from 0.8 Ω/km up to 8000 Ω/km as well as a complete range of components for connection and splicing of the cables.

Application

Area Classification:

  • Hazardous area, Zone 1 or Zone 2 (Gas) or Zone 21 or Zone 22 (Dust)
  • Ordinary area

Chemical Resistance:

  • Organic and inorganic corrosives

Approvals

  • System (heating units) PTB 08 ATEX 1102X
  • II 2G/D Ex e II T2...T6 / Ex tD A21 IP65 T290...T80°C
  • IECEx PTB 08.0051X
  • Ex II 2G/D Ex e II T2...T6 / Ex tD A21 IP65 T290...T80°C
  • PTB 08 ATEX 1088 U
  • II 2G/D Ex e II / Ex tD A21
  • IECEx PTB 08.0049 U
  • Ex II 2G/D Ex e II / Ex tD A21
Order Reference

Nominal Resistance

[Ω/km @ 20°C]

Temp Coefficient

[x 10-3 /K]

Outer Diameter

[mm nom.]

XPI-S-0.80.84.311.9
XPI-S-1.11.14.310.1
XPI-S-1.81.84.38.6
XPI-S-2.92.94.37.1
XPI-S-4.44.44.36.5
XPI-S-77.04.35.9
XPI-S-1010.04.35.8
XPI-S-11.711.74.35.6
XPI-S-15154.35.5
XPI-S-17.817.84.35.3
XPI-S-25253.05.5
XPI-S-31.531.51.35.9
XPI-S-50501.35.5
XPI-S-65651.35.4
XPI-S-80800.75.7
XPI-S-1001000.45.8
XPI-S-1501500.45.8
XPI-S-1801800.335.6
XPI-S-2002000.405.7
XPI-S-3203200.185.8
XPI-S-380380

0.18

5.7
XPI-S-4804800.185.6
XPI-S-6006000.185.4
XPI-S-7007000.185.4
XPI-S-8108100.045.5
XPI-S-100010000.045.4
XPI-S-144014400.045.4
XPI-S-175017500.045.6
XPI-S-200020000.355.5
XPI-S-300030000.355.8
XPI-S-400040000.355.6
XPI-S-440044000.15.5
XPI-S-516051600.15.5
XPI-S-560056000.15.4
XPI-S-700070000.15.4
XPI-S-800080000.15.3

Technical specifications

Max Exposure Temp260°C (power of, continuous), 300°C (power off, intermittent for max 1000h)
Maximum Power Output35 W/m (typical value, depending on application)
Maximum Power Output5 W/m (typical value, depending on application)
Min Bending Radius2.5 x cable diameter for cable diameter < 6mm
Min Bending Radius6 x cable diameter for cable diameter > 6mm
Minimum Clearance20 mm
Minimum installation temperature-70 °C
Nominal VoltageUp to 450/750 Vac (U0/U)

Product downloads

More from the Pentair Raychem XPI-S Trace Heating Cable range...