Raychem XPI-NH-15 Heating Cable 15 ?/km
Quick Find: 9399
Part Code: 1244-003091
Price on Application
Please contact our sales team for pricing.
Call us on
E-mail us at
Contact us online
Product overview
Range | Pentair Raychem XPI-NH Heating Cable |
---|---|
Model | XPI-NH-15 |
XPI-NH is a polymer insulated (PI) series heating cable, for use in non-hazardous areas. It has been designed for use in freeze protection and temperature maintenance applications of pipes, tanks and other equipment. XPI-NH offers an economical solution for a wide variety of heat-tracing applications in non-hazardous areas, in particular for pipe lengths beyond the maximum circuit lengths of parallel heating cables.
The selection of PTFE for the inner and outer insulation makes XPI-NH a safe and reliable product. It provides highest chemical withstand and good mechanical strength, in particular at elevated temperatures.
XPI-NH heating cables can be used for temperatures up to 260°C. The heating cable is easy to install and has printed meter-marks. Pentair Thermal Management offers XPI-NH heating cables in a very wide range of resistances, starting from 0.8 Ω/km up to 8000 Ω/km as well as a complete range of components for connection and splicing of the cables.
Apllication
Area Classification;
- Ordinary Areas
Chemical Resistance:
- Organics and corrosives
Order Reference | Nominal Resistance [Ω/km @ 20°C] | Temp Coefficient [x 10-3 /K] | Outer Diameter [mm nom.] |
---|---|---|---|
XPI-NH-0.8 | 0.8 | 4.3 | 11.5 |
XPI-NH-1.1 | 1.1 | 4.3 | 9.7 |
XPI-NH-1.8 | 1.8 | 4.3 | 8.2 |
XPI-NH-2.9 | 2.9 | 4.3 | 6.5 |
XPI-NH-4.4 | 4.4 | 4.3 | 5.5 |
XPI-NH-7 | 7.0 | 4.3 | 4.9 |
XPI-NH-10 | 10.0 | 4.3 | 4.4 |
XPI-NH-11.7 | 11.7 | 4.3 | 4.2 |
XPI-NH-15 | 15 | 4.3 | 4.1 |
XPI-NH-17.8 | 17.8 | 4.3 | 3.9 |
XPI-NH-25 | 25 | 3.0 | 3.9 |
XPI-NH-31.5 | 31.5 | 1.3 | 4.3 |
XPI-NH-50 | 50 | 1.3 | 3.9 |
XPI-NH-65 | 65 | 1.3 | 3.8 |
XPI-NH-80 | 80 | 0.7 | 4.1 |
XPI-NH-100 | 100 | 0.4 | 4.2 |
XPI-NH-150 | 150 | 0.4 | 3.9 |
XPI-NH-180 | 180 | 0.33 | 3.7 |
XPI-NH-200 | 200 | 0.40 | 3.8 |
XPI-NH-320 | 320 | 0.18 | 3.9 |
XPI-NH-380 | 380 | 0.18 | 3.8 |
XPI-NH-480 | 480 | 0.18 | 3.7 |
XPI-NH-600 | 600 | 0.18 | 3.8 |
XPI-NH-700 | 700 | 0.18 | 3.7 |
XPI-NH-810 | 810 | 0.04 | 3.5 |
XPI-NH-1000 | 1000 | 0.04 | 3.5 |
XPI-NH-1440 | 1440 | 0.04 | 3.4 |
XPI-NH-1750 | 1750 | 0.04 | 3.4 |
XPI-NH-2000 | 2000 | 0.35 | 3.6 |
XPI-NH-3000 | 3000 | 0.35 | 3.4 |
XPI-NH-4000 | 4000 | 0.35 | 3.4 |
XPI-NH-4400 | 4400 | 0.1 | 3.4 |
XPI-NH-5160 | 5160 | 0.1 | 3.4 |
XPI-NH-5600 | 5600 | 0.1 | 3.4 |
XPI-NH-7000 | 7000 | 0.1 | 3.4 |
XPI-NH-8000 | 8000 | 0.1 | 3.4 |
Technical specifications
Max Exposure Temp | 260°C (power off, continuous) |
---|---|
Max Exposure Temp | 260°C (power of, continuous) |
Maximum Power Output | 25 W/m (Typical value, depending on application) |
Min Bending Radius | 6 x cable diameter at -60°C |
Min Bending Radius | 2.5 x cable diameter at -25°C |
Min Installation Temp | -60°C |
Minimum Clearance | 20 mm |
Minimum installation temperature | -60 °C |
Nominal mains voltage/range | Up to 300/500 V |
Nominal Voltage | Up to 300/500 Vac (U/U) |
Product downloads
Frequently asked questions
Can I use heat trace on plastic pipes?
Yes, when using trace heating on plastic pipes ensure that ATE- 180 aluminium tape is used to help disperse the heat around the pipe.
Can you design a full surface heating system for me?
Yes, utilising our in-house design facilities, we can design your complete trace heating requirement.
Do I have to allow extra heat for pumps and valves?
If the surface area of the pump is substantially greater than that of the adjoining pipework then extra heating cable may need to be considered (depending on wattage of cable installed). Pumps and ...
Do I have to spiral the trace heating onto the pipe?
Most applications can simply be straight traced, reducing costs of materials and installation time without compromising on operational requirements.
Do I need to use thermal insulation?
Yes, thermal insulation is required on all heat trace applications. Without insulation, surface heat losses can increase approximately 4-5 times.
Does my trace heating system require maintenance?
Generally, no maintenance of our trace heating systems is required but it is recommended that the system is checked for operational and electrical integrity periodically or prior to the winter or p...
How do I terminate the heating cable?
Full termination instructions are provided with all our heating tapes
How do I test my trace heating system is working properly?
System checks depend on the system installed, constant wattage systems can be fully checked for insulation resistance and continuity. Self regulating systems can only be checked for insulation resi...
What is heat tape for water pipes?
When water pipes are exposed to cold temperatures either outdoors, underground or in small spaces, you can protect them from freezing by wrapping them with heat tape. Heating tape is actually a cor...
What is Heat Trace?
This is used for a pipe freeze protection application. Electric heat tracing, heat tape or surface heating, is a system used to maintain or raise the temperature of pipes and vessels. Trace heat...
What is self regulating heating tape?
Self limiting / self regulating heating tape adjusts heat output to equal the heat loss from the pipe work. As pipe temperature falls the electrical conductivity of the semi-conductive core increas...