Raychem HCH1M630 Sheathed Series Heating Cable 630 ?/km ATEX
Product overview
Raychem HCH/HCC mineral insulated (MI) Copper series heating cables are suited for use in hazardous areas. They are extensively used in a wide variety of industrial heat-tracing applications, such as long line heating or condensation prevention at low temperatures, and domestic applications, such as under ï¬Âoor or road and ramp heating applications. The copper heating cables with copper conductors (HCC) are available in very low resistances to allow for long line applications with a limited amount of supply points when the maximum operating sheath temperature does not exceed 200°C.
The typical maximum power output goes up to 50 W/m. Optionally they are offered with an HDPE (High Density Polyethylene) over-sheath for enhanced corrosion protection up to 80°C, usually applied when buried in concrete. For temperatures in excess of 80°C, an FEP (Fluorinated Ethylene Propylene) over-sheath is available which can be used up to a maximum temperature of 200°C.
The heating cables are offered as bulk cable as well as factory-terminated heating units to ensure optimum quality of the connections. The offering is completed with a full range of components for installation, connection and splicing of the heating cables.
Application
Area classification:
- Hazardous areas*, Zone 1 or Zone 2 (Gas) or Zone 21 or Zone 22 (Dust)
- Ordinary areas
- *cable types HCH1L2000 and HCH1L1250 can only be used in ordinary areas
Approvals
- Baseefa02ATEX0046X
- II 2GD Ex e II T6 to T3 Ex tD A21 IP6X
- Actual T class temperature determined by design
- Baseefa02ATEX0045U
- II 2G Ex e II
Order Reference | Nominal Resistance [Ω/km @ 20°C] | Temp Coefficient [x 10-3 /K] | Outer Diameter [mm nom.] | Max Coil Length (Kg/Km) |
---|---|---|---|---|
HCH1l2000 | 2000 | 2.8 | 0.4 | 1200 |
HCH1l1250 | 1250 | 2.8 | 0.4 | 1200 |
HCH1M800 | 800 | 3.5 | 0.4 | 900 |
HCH1M630 | 630 | 4.0 | 0.4 | 1100 |
HCH1M450 | 450 | 4.0 | 0.4 | 1000 |
HCH1M315 | 315 | 4.3 | 0.4 | 1000 |
HCH1M220 | 220 | 4.5 | 0.4 | 1000 |
HCH1M140 | 140 | 4.9 | 0.4 | 1000 |
HCH1M100 | 100 | 5.2 | 0.4 | 800 |
HCH1M63 | 63 | 3.2 | 0.4 | 2000 |
HCH1M40 | 40 | 3.4 | 3.9 | 2000 |
HCH1M25 | 25 | 3.7 | 3.9 | 1600 |
HCH1M17 | 17 | 4.6 | 3.9 | 500 |
HCH1M11 | 22 | 4.9 | 3.9 | 500 |
HCH1M7 | 7 | 5.3 | 3.9 | 400 |
HCH1M4 | 4 | 5.9 | 3.9 | 800 |
HCH1M2.87 | 2.87 | 6.4 | 3.9 | 650 |
HCH1M1.72 | 1.72 | 7.3 | 3.9 | 500 |
HCH1M1.08 | 1.08 | 8.3 | 3.9 | 400 |
Brass glands are standard on all heating units. Other materials are possible, contact Pentair for more information.
Delivery length of bulk cable on coil depends on type of resistance and is limited by max. coil length as indicated in the table on top. Factory terminated elements are limited by a max. weight of 50kg, however to ensure practical and safe on-site handling, it is strongly recommended to limit element lengths to 25 - 30kg. Not all resistances are standard items and as such may not be in stock.
Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as speciï¬Âed by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven.
Also refer to the components section for more details on heating units, accessories and nomenclatures.
Technical specifications
Brand | nVent |
---|---|
Cable sheath material | Copper |
Conductor Material | Copper (HCC) or Copper Alloy (HCH) |
Earth Leakage | 3 mA/100m (nominal at 20°C, 230Vac, 50-60Hz) |
Max Exposure Temp | 200°C |
Min Cable Spacing | 25mm for hazardous Areas |
Minimum installation temperature | -60 °C |