Raychem HAA2M13.2K Alloy 825 Sheathed Series Heating Cable (Dual, 300V) 13200 ?/km ATEX
Quick Find: 9567
Part Code: 32SA2400
Price on Application
Please contact our sales team for pricing.
Call us on
E-mail us at
Contact us online
Product overview
Model | HAA2M13.2K |
---|
Raychem HAx mineral insulated (MI) Alloy 825 series heating cables are suitable for use in hazardous areas. They have been designed for use in freeze protection and temperature maintenance applications of pipes, tanks and other equipment.
MI heating cables of the HAx-series offer an ideal combination of ruggedness, high temperature withstand capability and corrosion resistance and can therefore be used for a wide variety of heat-tracing applications, in particular for applications with high power requirements and for temperatures exceeding the capabilities of polymer insulated (PI) series heating cables.
The heating cables can be used for exposure temperatures of up to 700°C and a typical power output of up to 270 W/m. Higher temperatures and power outputs can be achieved, contact Pentair for assistance.
HAx mineral insulated (MI) heating cables are available as single and dual conductor construction and in a very wide range of resistances. The use of dual conductor heating cables can significantly reduce total installed cost and simplifies installation, in particular for small pipes and instrument tubing.
The heating cables are offered as bulk cable as well as factory terminated heating units employing brazing and laser welding technology. The offering is completed with a full range of components for installation, connection and splicing of the heating cables.
Application
Area Classification:
- Hazardous area, Zone 1 or Zone 2 (Gas) or Zone 21 or zone 22 (Dust)
- Ordinary
Approvals
System (Heating Units):
- Baseefa02ATEX0046X
- II 2GD Ex e II T6 to T1 Ex tD A21 IP6X
Order Reference | Nominal Resistance [Ω/km @ 20°C] | Temp Coefficient [x 10-3 /K] | Outer Diameter [mm nom.] | Max Coil Length (Kg/Km) | Part Number |
---|---|---|---|---|---|
HAF2M36K | 36000 | 0.09 | 11.5 | 628 | 32SF1110 |
HAF2M29.5K | 29500 | 0.09 | 9.7 | 542 | 32SF2900 |
HAF2M24.5K | 24500 | 0.09 | 8.2 | 431 | 32SF2750 |
HAA2M19.7K | 19700 | 0.09 | 6.5 | 632 | 32SA2600 |
HAA2M13.2K | 13200 | 0.09 | 5.5 | 500 | 32SA2400 |
HAA2M9000 | 9000 | 0.09 | 4.9 | 501 | 32SA2275 |
HAA2M6600 | 6600 | 0.09 | 4.4 | 329 | 32SA2200 |
HAA2M5600 | 5600 | 0.09 | 4.2 | 384 | 32SA2170 |
HAB2M3750 | 3750 | 0.04 | 4.1 | 315 | 32SB2114 |
HAB2M2300 | 2300 | 0.04 | 3.9 | 419 | 32SB3700 |
HAQ2M1560 | 1560 | 0.5 | 3.9 | 317 | 32SQ3472 |
HAQ2M1240 | 1240 | 0.5 | 4.3 | 317 | 32SQ3374 |
HAQ2M965 | 965 | 0.5 | 3.9 | 314 | 32SQ3293 |
HAQ2M660 | 660 | 0.5 | 3.8 | 503 | 32SQ3200 |
HAQ2M495 | 495 | 0.5 | 4.1 | 419 | 32SQ3150 |
HAQ2M330 | 330 | 0.5 | 4.2 | 332 | 32SQ3100 |
HAP2M240 | 240 | 1.3 | 3.9 | 316 | 32SP4734 |
HAP2M190 | 190 | 1.3 | 3.7 | 317 | 32SP4583 |
HAP2M150 | 150 | 1.3 | 3.8 | 315 | 32SP4458 |
HAC2M105 | 105 | 3.9 | 3.8 | 315 | 32SC4324 |
HAF2N36K | 36000 | 0.09 | 5.2 | 229 | 62SF1110 |
HAF2N29.5K | 29500 | 0.09 | 5.5 | 229 | 62SF2900 |
HAF2N19.7K | 19700 | 0.09 | 5.5 | 230 | 62SF2600 |
HAA2N13.6K | 13600 | 0.09 | 5.8 | 186 | 62SA2414 |
HAF2N6600 | 6600 | 0.09 | 6.3 | 177 | 62SF2200 |
HAT2N3750 | 3750 | 0.04 | 5.7 | 186 | 62ST2115 |
HAB2N2300 | 2300 | 0.5 | 6.8 | 151 | 62SB3700 |
HAQ2N1670 | 1670 | 0.5 | 5.7 | 194 | 62SQ3505 |
HAQ2N940 | 940 | 0.5 | 6.0 | 176 | 62SQ3286 |
HAQ2N660 | 660 | 0.5 | 6.3 | 177 | 62SQ3200 |
HAQ2N495 | 495 | 0.5 | 6.3 | 177 | 62SQ3150 |
HAQ2N330 | 330 | 1.3 | 6.7 | 152 | 62SQ3100 |
HAP2N255 | 255 | 1.3 | 6.4 | 151 | 62SP4775 |
HAP2N185 | 185 | 1.3 | 6.7 | 138 | 62SP4561 |
HAP2N130 | 130 | 1.3 | 7.1 | 124 | 62SP4402 |
HAP2N92 | 92 | 3.9 | 7.5 | 110 | 62SP4281 |
HAC2N66 | 66 | 3.9 | 7.5 | 131 | 62SC4200 |
HAC2N43 | 43 | 3.9 | 7.9 | 115 | 62SC4130 |
HAC2N27 | 27 | 3.9 | 8.7 | 98 | 62SC5818 |
HAC2N17 | 17 | 3.9 | 9.2 | 81 | 62SC5516 |
HAC2N10.5 | 10.2 | 3.9 | 10.2 | 67 | 62SC5324 |
HAC2N6.6 | 12.6 | 3.9 | 12.2 | 46 | 62SC5204 |
HAC2N4.3 | 13.8 | 3.9 | 13.8 | 143 | 62SC5128 |
HAA1N6565 | 6565 | 0.085 | 3.7 | 519 | 61SA2200 |
HAA1N5250 | 5250 | 0.085 | 4.1 | 436 | 61SA2160 |
HAA1N4300 | 4300 | 0.085 | 4.1 | 415 | 61SA2130 |
HAA1N3300 | 3300 | 0.085 | 4.0 | 416 | 61SA2100 |
HAA1N2800 | 2800 | 0.085 | 4.3 | 368 | 61SA3850 |
HAA1N2300 | 2300 | 0.085 | 4.1 | 417 | 61SA3700 |
HAA1N1640 | 1640 | 0.085 | 4.5 | 329 | 61SA3500 |
HAT1N920 | 920 | 0.18 | 4.6 | 317 | 61ST3280 |
HAB1N660 | 660 | 0.04 | 4.6 | 330 | 61SB3200 |
HAB1N500 | 500 | 0.04 | 4.6 | 331 | 61SB3150 |
HAQ1N390 | 390 | 0.5 | 4.7 | 317 | 61SQ3118 |
HAQ1N240 | 240 | 0.5 | 4.7 | 314 | 61SQ4732 |
HAQ1N190 | 190 | 0.5 | 4.6 | 342 | 61SQ4581 |
HAP1N155 | 155 | 1.3 | 4.7 | 316 | 61SP4467 |
HAP1N120 | 120 | 1.3 | 4.7 | 314 | 61SP4366 |
HAP1N95 | 95 | 1.3 | 4.7 | 315 | 61SP4290 |
HAP1N76 | 76 | 1.3 | 4.6 | 342 | 61SP4231 |
HAP1N60 | 60 | 1.3 | 4.7 | 316 | 61SP4183 |
HAP1N48 | 48 | 1.3 | 4.7 | 317 | 61SP4145 |
HAP1N37 | 37 | 1.3 | 4.7 | 335 | 61SP4113 |
HAC1N21.3 | 21.3 | 3.9 | 4.9 | 305 | 61SC5651 |
HAC1N13.5 | 13.5 | 3.9 | 5.1 | 294 | 61SC5409 |
HAC1N8.5 | 8.5 | 3.9 | 5.6 | 233 | 61SC5258 |
HAC1N5.3 | 5.3 | 3.9 | 6.9 | 158 | 61SC5162 |
HAC1N3.3 | 3.3 | 3.9 | 6.4 | 171 | 61SC5102 |
HAC1N2 | 2.0 | 3.9 | 8.1 | 115 | 61SC6640 |
All cold lead cables can be used for up to 600 Vac and use copper conductors with a temperature coefficient of 3.9 x 10-3 1/K. * For details on the different heating unit designs, refer to page 179.
Delivery length of bulk cable on coil depends on type of resistance and is limited by max. coil length as indicated in the table on top.
Factory terminated elements are limited by a max. weight of 50kg, however to ensure practical and safe on-site handling, it is strongly recommended to limit element lengths to 25 - 30kg. Not all resistances are standard items and as such may not be in stock. Contact Pentair to confirm lead time. Pentair requires the use of a 30 mA residual current device to provide maximum safety and protection from fire.
Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven.
Technical specifications
Cable Sheath Material | Alloy 825 |
---|---|
Conductor Material | Various Alloys and Copper |
Earth Leakage | 3 mA/100m (Nominal at 20°C, 230 Vac, 50-60 Hz) |
Max Exposure Temp | 700°C (Laser Welded Heating Units) |
Max Exposure Temp | 550°C (Brazed Heating Units) |
Max Exposure Temp | 700°C (Heating Cables) |
Min Bending Radius | 6 x outer diameter at -60°C |
Min Cable Spacing | 25mm for hazardous Areas |
Frequently asked questions
Can I use heat trace on plastic pipes?
Yes, when using trace heating on plastic pipes ensure that ATE- 180 aluminium tape is used to help disperse the heat around the pipe.
Can you design a full surface heating system for me?
Yes, utilising our in-house design facilities, we can design your complete trace heating requirement.
Do I have to allow extra heat for pumps and valves?
If the surface area of the pump is substantially greater than that of the adjoining pipework then extra heating cable may need to be considered (depending on wattage of cable installed). Pumps and ...
Do I have to spiral the trace heating onto the pipe?
Most applications can simply be straight traced, reducing costs of materials and installation time without compromising on operational requirements.
Do I need to use thermal insulation?
Yes, thermal insulation is required on all heat trace applications. Without insulation, surface heat losses can increase approximately 4-5 times.
Does my trace heating system require maintenance?
Generally, no maintenance of our trace heating systems is required but it is recommended that the system is checked for operational and electrical integrity periodically or prior to the winter or p...
How do I terminate the heating cable?
Full termination instructions are provided with all our heating tapes
How do I test my trace heating system is working properly?
System checks depend on the system installed, constant wattage systems can be fully checked for insulation resistance and continuity. Self regulating systems can only be checked for insulation resi...
What is heat tape for water pipes?
When water pipes are exposed to cold temperatures either outdoors, underground or in small spaces, you can protect them from freezing by wrapping them with heat tape. Heating tape is actually a cor...
What is Heat Trace?
This is used for a pipe freeze protection application. Electric heat tracing, heat tape or surface heating, is a system used to maintain or raise the temperature of pipes and vessels. Trace heat...
What is self regulating heating tape?
Self limiting / self regulating heating tape adjusts heat output to equal the heat loss from the pipe work. As pipe temperature falls the electrical conductivity of the semi-conductive core increas...