Raychem 5KTV2-CT Self Regulating Trace Heating Cable

More from KTV Self Regulating Heating Cable

Raychem 5KTV2-CT Self Regulating Trace Heating Cable
Raychem 5KTV2-CT Self Regulating Trace Heating Cable
Raychem 5KTV2-CT Self Regulating Trace Heating Cable
Free Delivery Available
£52.50
£63.00 inc VAT
List Price: £56.00

Selected Total: £0.00


    Qty

    Product overview

    Weight 0.25 Kg

    Electrical heat-tracing for process temperature maintenance applications up to 150°C which may be subject to steam cleaning.

    The nVent RAYCHEM KTV family of self-regulating, parallel circuit heating cables is used for process temperature maintenance of pipes and vessels.

    It can also be used for frost protection of large pipes and for applications requiring high temperature exposure capability.

    Application

    Area Classification:

    • Hazardous, Zone 1, Zone 2(Gas), Zone 21, Zone 22 (Dust)
    • Ordinary

    Traced Surface Type:

    • Carbon Steel
    • Stainless Steel
    • Painted or Unpainted Metal

    Chemical Resistance:

    • Organics and corrosives

    Approvals

    The KTV heating cables are approved for use in hazardous areas by PTB and Baseefa Ltd.

    • PTB 09 ATEX 1117 X & Baseefa06ATEX0186X
    • II 2G Ex e II 226°C (T2) & II 2D Ex tD A21 IP66 T226°C
    • IECEx PTB 09.0058X & IECEx BAS 06.0046X
    • Ex e II 226°C (T2) & Ex tD A21 IP66 T226°C

    Maximum Circuit Length

    Based on Type 'C' Circuit Breakers According to EN 60898

    Electrical Protection SizingStart Up TemperatureMaximum Heating Cable length per circuit(M)
    16 A-20°c130956040
    +10°c1451056545
    25 A-20°c2051509065
    +10°c23016510075
    32 A-20°c23018011585
    +10°c23018013095
    40 A-20°c230180130105
    +10°c230180130110

    The above numbers are for circuit length estimation only. For more detailed information please use the Pentair TraceCalc software or contact your local Pentair representative. Pentair requires the use of a 30 mA residual current device to provide maximum safety and protection from fire.

    Where design results in higher leakage current, the preferred trip level for adjustable devices is 30 mA above any inherent capacitive leakage characteristic of the heater as specified by the trace heater supplier or alternatively, the next common available trip level for non adjustable devices, with a maximum of 300 mA. All safety aspects need to be proven.

     

    Technical specifications

    BrandnVent
    Max Exposure Temp110 °C
    Maximum maintain or continuous exposure temperature (power on)110 °C
    Minimum bend radiusAt 20°C: 26 mm
    Minimum installation temperature-60 °C
    Model5KTV2-CT
    Nominal Power Output16 W/m @ 10 °C
    Temperature ClassificationT2 in accordance with European Standard EN 60079-30-1 5.1.13
    Thickness7.6 mm
    Width13.3 mm

    Videos

    Product downloads

    10-Year Warranty

    File Size: 514.61 KB

    Data Sheet

    File Size: 383.72 KB

    Data Sheet

    File Size: 10.10 MB

    Declarations of Conformity

    File Size: 145.45 KB

    DNV Approval Certificate

    File Size: 203.71 KB

    More from the Pentair Raychem KTV Self Regulating Heating Cable range...